Backflow assembly test: 9784 Spring Branch Ln

Approved

Filed Jun 11, 2025 by Riley Marsh, Valley Plumbing & Backflow. Read in from a paper form and confirmed by staff.

Report

Date of service
Jun 11, 2025
Assembly type
DC
Serial number
A978254
Size
3/4
Test gauge serial
G-7227
Gauge calibration date
Jan 6, 2025
Check valve 1
3.7 psid
Check valve 1 closed tight
Yes
Check valve 2
3.7 psid
Result
Pass
I certify this report is true and that I performed or supervised the work
Yes

Automatic checks

  • License on file for Riley Marsh, current on the service date
  • All required fields present
  • Address matches parcel 017-32-01100
  • Readings in range, no flags
  • Result: passing. Next due date resets when approved.

Decision

Approved by M. Reviewer. The property's next due date is set and the owner gets a receipt.

Property

9784 Spring Branch Ln
Owner: Morgan Nguyen
Parcel 017-32-01100