Backflow assembly test: 5187 Old Church Dr

Approved

Filed Oct 5, 2026 by Reese Fairley, Keystone Backflow Testing. Read in from a paper form and confirmed by staff.

Report

Date of service
Oct 5, 2026
Assembly type
RP
Serial number
B834197
Size
3/4
Test gauge serial
G-6005
Gauge calibration date
Feb 2, 2026
Check valve 1
3.4 psid
Check valve 1 closed tight
Yes
Check valve 2
2.3 psid
Relief valve opened at
2.4 psid
Result
Pass
I certify this report is true and that I performed or supervised the work
Yes

Automatic checks

  • License on file for Reese Fairley, current on the service date
  • All required fields present
  • Address matches parcel 025-55-01107
  • Readings in range, no flags
  • Result: passing. Next due date resets when approved.

Decision

Approved automatically, because nothing was flagged. The property's next due date is set and the owner gets a receipt.