Back to the backflow review queue

Backflow assembly test: 1926 Fox Run Trl

Approved

Filed May 3, 2024 by Emerson Ellery, Valley Plumbing & Backflow. Filed from a phone.

Report

Date of service
May 3, 2024
Assembly type
RP
Serial number
W526821
Size
3/4
Test gauge serial
G-5561
Gauge calibration date
Apr 2, 2024
Check valve 1
7.6 psid
Check valve 1 closed tight
Yes
Check valve 2
1.3 psid
Relief valve opened at
2.7 psid
Result
Pass
I certify this report is true and that I performed or supervised the work
Yes

Automatic checks

  • License on file for Emerson Ellery, current on the service date
  • All required fields present
  • Address matches parcel 025-45-01224
  • Readings in range, no flags
  • Result: passing. Next due date resets when approved.

Decision

Approved by M. Reviewer. The property's next due date is set and the owner gets a receipt.

Property

1926 Fox Run Trl
Owner: Jamie Lindqvist
Parcel 025-45-01224