Back to the backflow review queue

Backflow assembly test: 1926 Fox Run Trl

Approved

Filed May 14, 2025 by Hayden Marsh, Valley Plumbing & Backflow. Filed from a phone.

Report

Date of service
May 14, 2025
Assembly type
RP
Serial number
W526821
Size
3/4
Test gauge serial
G-3508
Gauge calibration date
Mar 12, 2025
Check valve 1
8.6 psid
Check valve 1 closed tight
Yes
Check valve 2
2.8 psid
Relief valve opened at
3.8 psid
Result
Pass
I certify this report is true and that I performed or supervised the work
Yes

Automatic checks

  • License on file for Hayden Marsh, current on the service date
  • All required fields present
  • Address matches parcel 025-45-01224
  • Readings in range, no flags
  • Result: passing. Next due date resets when approved.

Decision

Approved by M. Reviewer. The property's next due date is set and the owner gets a receipt.

Property

1926 Fox Run Trl
Owner: Jamie Lindqvist
Parcel 025-45-01224