Backflow assembly test: 3745 Ridgeview Trl

Approved

Filed May 19, 2025 by Parker Benton, Keystone Backflow Testing. Filed from a phone.

Report

Date of service
May 19, 2025
Assembly type
RP
Serial number
W551497
Size
1
Test gauge serial
G-2915
Gauge calibration date
Aug 1, 2024
Check valve 1
9 psid
Check valve 1 closed tight
Yes
Check valve 2
1.9 psid
Relief valve opened at
4 psid
Result
Pass
I certify this report is true and that I performed or supervised the work
Yes

Automatic checks

  • License on file for Parker Benton, current on the service date
  • All required fields present
  • Address matches parcel 025-65-01047
  • Readings in range, no flags
  • Result: passing. Next due date resets when approved.

Decision

Approved by J. Staff. The property's next due date is set and the owner gets a receipt.

Property

3745 Ridgeview Trl
Owner: Casey Vance
Parcel 025-65-01047