Back to the backflow review queue

Backflow assembly test: 4525 Ridgeview Trl

Approved

Filed Sep 12, 2024 by Emerson Ellery, Valley Plumbing & Backflow. Filed from a phone.

Report

Date of service
Sep 12, 2024
Assembly type
RP
Serial number
Z840246
Size
1
Test gauge serial
G-1450
Gauge calibration date
Jun 20, 2024
Check valve 1
4.5 psid
Check valve 1 closed tight
Yes
Check valve 2
2.4 psid
Relief valve opened at
3.4 psid
Result
Pass
I certify this report is true and that I performed or supervised the work
Yes

Automatic checks

  • License on file for Emerson Ellery, current on the service date
  • All required fields present
  • Address matches parcel 025-65-01343
  • Readings in range, no flags
  • Result: passing. Next due date resets when approved.

Decision

Approved by M. Reviewer. The property's next due date is set and the owner gets a receipt.

Property

4525 Ridgeview Trl
Owner: Jordan Vance
Parcel 025-65-01343