Back to the backflow review queue

Backflow assembly test: Main Street Bakery

Approved

Filed Nov 9, 2026 by Hayden Marsh, Valley Plumbing & Backflow. Filed from a phone.

Report

Date of service
Nov 9, 2026
Assembly type
DC
Serial number
B120377
Size
1
Test gauge serial
G-6806
Gauge calibration date
Aug 17, 2026
Check valve 1
6.3 psid
Check valve 1 closed tight
Yes
Check valve 2
1.4 psid
Result
Pass
I certify this report is true and that I performed or supervised the work
Yes

Automatic checks

  • License on file for Hayden Marsh, current on the service date
  • All required fields present
  • Address matches parcel 025-80-01137
  • Readings in range, no flags
  • Result: passing. Next due date resets when approved.

Decision

Approved by M. Reviewer. The property's next due date is set and the owner gets a receipt.

Property

5950 Spring Branch Rd
Owner: Kessler Holdings LLC
Parcel 025-80-01137