Approved

Filed Oct 19, 2025 by Parker Benton, Keystone Backflow Testing. Filed from a phone.

Report

Date of service
Oct 19, 2025
Assembly type
RP
Serial number
W500932
Size
1
Test gauge serial
G-1561
Gauge calibration date
Dec 30, 2024
Check valve 1
7.6 psid
Check valve 1 closed tight
Yes
Check valve 2
1.2 psid
Relief valve opened at
2.4 psid
Result
Pass
I certify this report is true and that I performed or supervised the work
Yes

Automatic checks

  • License on file for Parker Benton, current on the service date
  • All required fields present
  • Address matches parcel 025-37-01103
  • Readings in range, no flags
  • Result: passing. Next due date resets when approved.

Decision

Approved by J. Staff. The property's next due date is set and the owner gets a receipt.