Backflow assembly test: 8831 Orchard Ct
ApprovedFiled Oct 3, 2024 by Reese Fairley, Keystone Backflow Testing. Read in from a paper form and confirmed by staff.
Report
- Date of service
- Oct 3, 2024
- Assembly type
- RP
- Serial number
- K341065
- Size
- 3/4
- Test gauge serial
- G-6617
- Gauge calibration date
- Apr 17, 2024
- Check valve 1
- 7.9 psid
- Check valve 1 closed tight
- Yes
- Check valve 2
- 1.1 psid
- Relief valve opened at
- 2.3 psid
- Result
- Pass
- I certify this report is true and that I performed or supervised the work
- Yes
Automatic checks
- License on file for Reese Fairley, current on the service date
- All required fields present
- Address matches parcel 025-63-01170
- Readings in range, no flags
- Result: passing. Next due date resets when approved.
Decision
Approved automatically, because nothing was flagged. The property's next due date is set and the owner gets a receipt.