Backflow assembly test: 8831 Orchard Ct

Approved

Filed Nov 13, 2026 by Hayden Marsh, Valley Plumbing & Backflow. Filed from a phone.

Report

Date of service
Nov 13, 2026
Assembly type
RP
Serial number
K341065
Size
3/4
Test gauge serial
G-6215
Gauge calibration date
Feb 23, 2026
Check valve 1
6.4 psid
Check valve 1 closed tight
Yes
Check valve 2
2.4 psid
Relief valve opened at
2.4 psid
Result
Pass
I certify this report is true and that I performed or supervised the work
Yes

Automatic checks

  • License on file for Hayden Marsh, current on the service date
  • All required fields present
  • Address matches parcel 025-63-01170
  • Readings in range, no flags
  • Result: passing. Next due date resets when approved.

Decision

Approved automatically, because nothing was flagged. The property's next due date is set and the owner gets a receipt.

Property

8831 Orchard Ct
Owner: Blake Whitcomb
Parcel 025-63-01170