Back to the backflow review queue

Backflow assembly test: Maple Leaf Market

Approved

Filed Aug 9, 2025 by Emerson Ellery, Valley Plumbing & Backflow. Filed from a phone.

Report

Date of service
Aug 9, 2025
Assembly type
RP
Serial number
W585556
Size
2
Test gauge serial
G-6388
Gauge calibration date
Dec 8, 2024
Check valve 1
4.6 psid
Check valve 1 closed tight
Yes
Check valve 2
2 psid
Relief valve opened at
3.4 psid
Result
Pass
I certify this report is true and that I performed or supervised the work
Yes

Automatic checks

  • License on file for Emerson Ellery, current on the service date
  • All required fields present
  • Address matches parcel 025-75-01346
  • Readings in range, no flags
  • Result: passing. Next due date resets when approved.

Decision

Approved by M. Reviewer. The property's next due date is set and the owner gets a receipt.

Property

8793 Old Church Trl
Owner: Marsh Holdings LLC
Parcel 025-75-01346