Backflow assembly test: 1435 Sycamore Trl

Filed Nov 25, 2026 by Avery Vance, Ridge Backflow Testing. Filed from a phone.

Report

Date of service
Nov 25, 2026
Assembly type
RP
Serial number
A719670
Size
3/4
Test gauge serial
G-3471
Gauge calibration date
Sep 11, 2026
Check valve 1
0.2 psid
Check valve 1 closed tight
No
Check valve 2
3.8 psid
Relief valve opened at
4 psid
Result
Fail
I certify this report is true and that I performed or supervised the work
Yes

Automatic checks

  • License on file for Avery Vance, current on the service date
  • All required fields present
  • Address matches parcel 025-94-01207
  • Readings in range, no flags
  • Result: needs follow-up. The property stays on the overdue list until a passing report arrives.