Backflow assembly test: 7113 Meadow Lark Rd
ApprovedFiled Oct 8, 2023 by Emerson Ellery, Valley Plumbing & Backflow. Filed from a phone.
Report
- Date of service
- Oct 8, 2023
- Assembly type
- DC
- Serial number
- W810888
- Size
- 1
- Test gauge serial
- G-6926
- Gauge calibration date
- Jul 2, 2023
- Check valve 1
- 7.8 psid
- Check valve 1 closed tight
- Yes
- Check valve 2
- 3.8 psid
- Result
- Pass
- I certify this report is true and that I performed or supervised the work
- Yes
Automatic checks
- License on file for Emerson Ellery, current on the service date
- All required fields present
- Address matches parcel 025-51-01160
- Readings in range, no flags
- Result: passing. Next due date resets when approved.
Decision
Approved by J. Staff. The property's next due date is set and the owner gets a receipt.
Property
7113 Meadow Lark Rd
Owner: Parker Ramirez
Parcel 025-51-01160