Backflow assembly test: 7050 Quarry Trl

Approved

Filed Jun 5, 2025 by Parker Whitcomb, Ridge Backflow Testing. Filed from a phone.

Report

Date of service
Jun 5, 2025
Assembly type
PVB
Serial number
K521095
Size
1
Test gauge serial
G-5886
Gauge calibration date
Oct 12, 2024
Check valve 1
6.6 psid
Check valve 1 closed tight
Yes
Check valve 2
1.9 psid
Result
Pass
I certify this report is true and that I performed or supervised the work
Yes

Automatic checks

  • License on file for Parker Whitcomb, current on the service date
  • All required fields present
  • Address matches parcel 037-71-01160
  • Readings in range, no flags
  • Result: passing. Next due date resets when approved.

Decision

Approved automatically, because nothing was flagged. The property's next due date is set and the owner gets a receipt.

Property

7050 Quarry Trl
Owner: Hayden Stroud
Parcel 037-71-01160