Backflow assembly test: Crossroads Grill

Approved

Filed Oct 14, 2024 by Parker Vance, Valley Backflow Testing. Filed from a phone.

Report

Date of service
Oct 14, 2024
Assembly type
RP
Serial number
W880786
Size
2
Test gauge serial
G-4979
Gauge calibration date
Mar 11, 2024
Check valve 1
5.4 psid
Check valve 1 closed tight
Yes
Check valve 2
1.3 psid
Relief valve opened at
2.3 psid
Result
Pass
I certify this report is true and that I performed or supervised the work
Yes

Automatic checks

  • License on file for Parker Vance, current on the service date
  • All required fields present
  • Address matches parcel 037-33-01123
  • Readings in range, no flags
  • Result: passing. Next due date resets when approved.

Decision

Approved by J. Staff. The property's next due date is set and the owner gets a receipt.

Property

5296 Fox Run Ln
Owner: Hollins Holdings LLC
Parcel 037-33-01123