Backflow assembly test: 8825 Orchard Rd

Approved

Filed Aug 5, 2025 by Drew Kessler, Heritage Backflow Testing. Filed from a phone.

Report

Date of service
Aug 5, 2025
Assembly type
PVB
Serial number
K242168
Size
3/4
Test gauge serial
G-8117
Gauge calibration date
Mar 19, 2025
Check valve 1
8.1 psid
Check valve 1 closed tight
Yes
Check valve 2
3.4 psid
Result
Pass
I certify this report is true and that I performed or supervised the work
Yes

Automatic checks

  • License on file for Drew Kessler, current on the service date
  • All required fields present
  • Address matches parcel 037-24-01333
  • Readings in range, no flags
  • Result: passing. Next due date resets when approved.

Decision

Approved automatically, because nothing was flagged. The property's next due date is set and the owner gets a receipt.

Property

8825 Orchard Rd
Owner: Taylor Fairley
Parcel 037-24-01333