Backflow assembly test: 9231 Ridgeview Rd

Approved

Filed Dec 3, 2023 by Parker Vance, Valley Backflow Testing. Read in from a paper form and confirmed by staff.

Report

Date of service
Dec 3, 2023
Assembly type
PVB
Serial number
K842964
Size
3/4
Test gauge serial
G-2894
Gauge calibration date
May 20, 2023
Check valve 1
5.2 psid
Check valve 1 closed tight
Yes
Check valve 2
2.1 psid
Result
Pass
I certify this report is true and that I performed or supervised the work
Yes

Automatic checks

  • License on file for Parker Vance, current on the service date
  • All required fields present
  • Address matches parcel 037-94-01269
  • Readings in range, no flags
  • Result: passing. Next due date resets when approved.

Decision

Approved by M. Reviewer. The property's next due date is set and the owner gets a receipt.

Property

9231 Ridgeview Rd
Owner: Sam Nguyen
Parcel 037-94-01269