Backflow assembly test: 386 Orchard Trl

Approved

Filed Jun 1, 2025 by Parker Whitcomb, Ridge Backflow Testing. Filed from a phone.

Report

Date of service
Jun 1, 2025
Assembly type
PVB
Serial number
A505328
Size
1
Test gauge serial
G-9163
Gauge calibration date
Sep 20, 2024
Check valve 1
6.8 psid
Check valve 1 closed tight
Yes
Check valve 2
3.5 psid
Result
Repaired and passed
Repairs made
Replaced check valve 1 rubber
I certify this report is true and that I performed or supervised the work
Yes

Automatic checks

  • License on file for Parker Whitcomb, current on the service date
  • All required fields present
  • Address matches parcel 037-57-01118
  • Readings in range, no flags
  • Result: passing. Next due date resets when approved.

Decision

Approved by M. Reviewer. The property's next due date is set and the owner gets a receipt.