Backflow assembly test: 1687 Spring Branch Ln

Approved

Filed Oct 15, 2024 by Sam Vance, Heritage Backflow Testing. Filed from a phone.

Report

Date of service
Oct 15, 2024
Assembly type
RP
Serial number
Z285823
Size
3/4
Test gauge serial
G-7881
Gauge calibration date
Jul 31, 2024
Check valve 1
3.8 psid
Check valve 1 closed tight
Yes
Check valve 2
1.6 psid
Relief valve opened at
3.2 psid
Result
Pass
I certify this report is true and that I performed or supervised the work
Yes

Automatic checks

  • License on file for Sam Vance, current on the service date
  • All required fields present
  • Address matches parcel 037-19-01313
  • Readings in range, no flags
  • Result: passing. Next due date resets when approved.

Decision

Approved by M. Reviewer. The property's next due date is set and the owner gets a receipt.