Backflow assembly test: 1687 Spring Branch Ln
Sent backFiled Nov 21, 2026 by Parker Whitcomb, Ridge Backflow Testing. Filed from a phone.
Report
- Date of service
- Nov 21, 2026
- Assembly type
- RP
- Serial number
- Z285823
- Size
- 3/4
- Test gauge serial
- G-3354
- Gauge calibration date
- Jul 21, 2026
- Check valve 1
- 5.8 psid
- Check valve 1 closed tight
- Yes
- Check valve 2
- 3.3 psid
- Relief valve opened at
- 3.8 psid
- Result
- Pass
- I certify this report is true and that I performed or supervised the work
- Yes
Automatic checks
- License on file for Parker Whitcomb, current on the service date
- All required fields present
- Address matches parcel 037-19-01313
- Readings in range, no flags
- Result: passing. Next due date resets when approved.
Decision
Sent back Please add the test gauge calibration certificate.