Backflow assembly test: 7537 Sycamore Dr
ApprovedFiled Oct 30, 2025 by Parker Vance, Valley Backflow Testing. Read in from a paper form and confirmed by staff.
Report
- Date of service
- Oct 30, 2025
- Assembly type
- PVB
- Serial number
- A907690
- Size
- 1
- Test gauge serial
- G-3911
- Gauge calibration date
- Mar 22, 2025
- Check valve 1
- 7.3 psid
- Check valve 1 closed tight
- Yes
- Check valve 2
- 2.5 psid
- Result
- Pass
- I certify this report is true and that I performed or supervised the work
- Yes
Automatic checks
- License on file for Parker Vance, current on the service date
- All required fields present
- Address matches parcel 037-37-01054
- Readings in range, no flags
- Result: passing. Next due date resets when approved.
Decision
Approved by M. Reviewer. The property's next due date is set and the owner gets a receipt.