Backflow assembly test: 3429 Orchard Ln

Approved

Filed Oct 1, 2026 by Parker Vance, Valley Backflow Testing. Filed from a phone.

Report

Date of service
Oct 1, 2026
Assembly type
RP
Serial number
A465020
Size
1
Test gauge serial
G-5009
Gauge calibration date
Jun 12, 2025
Check valve 1
0.6 psid
Check valve 1 closed tight
No
Check valve 2
3.4 psid
Relief valve opened at
4.1 psid
Result
Fail
I certify this report is true and that I performed or supervised the work
Yes

Automatic checks

  • License on file for Parker Vance, current on the service date
  • All required fields present
  • Address matches parcel 037-46-01266
  • Test gauge calibration is more than a year old.
  • Result: needs follow-up. The property stays on the overdue list until a passing report arrives.

Decision

Approved by J. Staff. The property's next due date is set and the owner gets a receipt.