Backflow assembly test: 3429 Orchard Ln
ApprovedFiled Oct 1, 2026 by Parker Vance, Valley Backflow Testing. Filed from a phone.
Report
- Date of service
- Oct 1, 2026
- Assembly type
- RP
- Serial number
- A465020
- Size
- 1
- Test gauge serial
- G-5009
- Gauge calibration date
- Jun 12, 2025
- Check valve 1
- 0.6 psid
- Check valve 1 closed tight
- No
- Check valve 2
- 3.4 psid
- Relief valve opened at
- 4.1 psid
- Result
- Fail
- I certify this report is true and that I performed or supervised the work
- Yes
Automatic checks
- License on file for Parker Vance, current on the service date
- All required fields present
- Address matches parcel 037-46-01266
- Test gauge calibration is more than a year old.
- Result: needs follow-up. The property stays on the overdue list until a passing report arrives.
Decision
Approved by J. Staff. The property's next due date is set and the owner gets a receipt.
Property
3429 Orchard Ln
Owner: Jordan Ashby
Parcel 037-46-01266