Backflow assembly test: Hilltop Medical Offices
ApprovedFiled Dec 25, 2025 by Parker Vance, Valley Backflow Testing. Filed from a phone.
Report
- Date of service
- Dec 25, 2025
- Assembly type
- RP
- Serial number
- B947806
- Size
- 4
- Test gauge serial
- G-4012
- Gauge calibration date
- Apr 25, 2025
- Check valve 1
- 5.4 psid
- Check valve 1 closed tight
- Yes
- Check valve 2
- 2.4 psid
- Relief valve opened at
- 4 psid
- Result
- Pass
- I certify this report is true and that I performed or supervised the work
- Yes
Automatic checks
- License on file for Parker Vance, current on the service date
- All required fields present
- Address matches parcel 037-13-01081
- Readings in range, no flags
- Result: passing. Next due date resets when approved.