Back to the backflow review queue

Backflow assembly test: Corner Brewing Co

Approved

Filed Sep 28, 2023 by Parker Vance, Valley Backflow Testing. Filed from a phone.

Report

Date of service
Sep 28, 2023
Assembly type
RP
Serial number
Z611675
Size
4
Test gauge serial
G-9218
Gauge calibration date
Mar 9, 2023
Check valve 1
7.5 psid
Check valve 1 closed tight
Yes
Check valve 2
1.8 psid
Relief valve opened at
2.2 psid
Result
Pass
I certify this report is true and that I performed or supervised the work
Yes

Automatic checks

  • License on file for Parker Vance, current on the service date
  • All required fields present
  • Address matches parcel 037-65-01234
  • Readings in range, no flags
  • Result: passing. Next due date resets when approved.

Decision

Approved by J. Staff. The property's next due date is set and the owner gets a receipt.

Property

2194 Pine Knoll Ct
Owner: Brandt Holdings LLC
Parcel 037-65-01234