Backflow assembly test: Corner Brewing Co
ApprovedFiled Sep 7, 2025 by Parker Whitcomb, Ridge Backflow Testing. Read in from a paper form and confirmed by staff.
Report
- Date of service
- Sep 7, 2025
- Assembly type
- RP
- Serial number
- Z611675
- Size
- 4
- Test gauge serial
- G-4369
- Gauge calibration date
- Apr 11, 2025
- Check valve 1
- 5.3 psid
- Check valve 1 closed tight
- Yes
- Check valve 2
- 3.6 psid
- Relief valve opened at
- 3.8 psid
- Result
- Pass
- I certify this report is true and that I performed or supervised the work
- Yes
Automatic checks
- License on file for Parker Whitcomb, current on the service date
- All required fields present
- Address matches parcel 037-65-01234
- Readings in range, no flags
- Result: passing. Next due date resets when approved.
Decision
Approved by M. Reviewer. The property's next due date is set and the owner gets a receipt.
Property
2194 Pine Knoll Ct
Owner: Brandt Holdings LLC
Parcel 037-65-01234