ApprovedFiled Dec 17, 2025 by Hayden Pruitt, Heritage Backflow Testing. Filed from a phone.
Report
- Date of service
- Dec 17, 2025
- Assembly type
- RP
- Serial number
- Z422049
- Size
- 3/4
- Test gauge serial
- G-7791
- Gauge calibration date
- Sep 2, 2025
- Check valve 1
- 8.6 psid
- Check valve 1 closed tight
- Yes
- Check valve 2
- 1 psid
- Relief valve opened at
- 3.4 psid
- Result
- Pass
- I certify this report is true and that I performed or supervised the work
- Yes
Automatic checks
- License on file for Hayden Pruitt, current on the service date
- All required fields present
- Address matches parcel 037-36-01131
- Readings in range, no flags
- Result: passing. Next due date resets when approved.
Decision
Approved by J. Staff. The property's next due date is set and the owner gets a receipt.