Back to the backflow review queue

Backflow assembly test: 3095 Laurel Way

Approved

Filed Aug 22, 2025 by Parker Vance, Valley Backflow Testing. Filed from a phone.

Report

Date of service
Aug 22, 2025
Assembly type
DC
Serial number
A717270
Size
1
Test gauge serial
G-5071
Gauge calibration date
Nov 26, 2024
Check valve 1
5.5 psid
Check valve 1 closed tight
Yes
Check valve 2
3.7 psid
Result
Pass
I certify this report is true and that I performed or supervised the work
Yes

Automatic checks

  • License on file for Parker Vance, current on the service date
  • All required fields present
  • Address matches parcel 037-31-01294
  • Readings in range, no flags
  • Result: passing. Next due date resets when approved.

Decision

Approved automatically, because nothing was flagged. The property's next due date is set and the owner gets a receipt.

Property

3095 Laurel Way
Owner: Jordan Harlow
Parcel 037-31-01294