Back to the backflow review queue
Backflow assembly test: 3447 Turkey Hill Dr
ApprovedFiled Feb 14, 2026 by Parker Vance, Valley Backflow Testing. Filed from a phone.
Report
- Date of service
- Feb 14, 2026
- Assembly type
- RP
- Serial number
- A302697
- Size
- 1
- Test gauge serial
- G-1796
- Gauge calibration date
- Aug 7, 2025
- Check valve 1
- 4.6 psid
- Check valve 1 closed tight
- Yes
- Check valve 2
- 3.3 psid
- Relief valve opened at
- 3.3 psid
- Result
- Pass
- I certify this report is true and that I performed or supervised the work
- Yes
Automatic checks
- License on file for Parker Vance, current on the service date
- All required fields present
- Address matches parcel 037-54-01162
- Readings in range, no flags
- Result: passing. Next due date resets when approved.
Decision
Approved by M. Reviewer. The property's next due date is set and the owner gets a receipt.
Property
3447 Turkey Hill Dr
Owner: Blake Kessler
Parcel 037-54-01162