Backflow assembly test: 9142 Mill Creek Rd

Approved

Filed Feb 12, 2025 by Parker Vance, Valley Backflow Testing. Filed from a phone.

Report

Date of service
Feb 12, 2025
Assembly type
RP
Serial number
W990085
Size
1
Test gauge serial
G-8978
Gauge calibration date
Sep 22, 2024
Check valve 1
6.8 psid
Check valve 1 closed tight
Yes
Check valve 2
1.2 psid
Relief valve opened at
2.6 psid
Result
Pass
I certify this report is true and that I performed or supervised the work
Yes

Automatic checks

  • License on file for Parker Vance, current on the service date
  • All required fields present
  • Address matches parcel 037-13-01222
  • Readings in range, no flags
  • Result: passing. Next due date resets when approved.

Decision

Approved automatically, because nothing was flagged. The property's next due date is set and the owner gets a receipt.