Report

Date of service
Nov 21, 2026
Assembly type
RP
Serial number
W764151
Size
4
Test gauge serial
G-3340
Gauge calibration date
Apr 3, 2026
Check valve 1
3.9 psid
Check valve 1 closed tight
Yes
Check valve 2
3.9 psid
Relief valve opened at
3.5 psid
Result
Pass
I certify this report is true and that I performed or supervised the work
Yes

Automatic checks

  • License on file for Hayden Pruitt, current on the service date
  • All required fields present
  • Address matches parcel 037-60-01330
  • Readings in range, no flags
  • Result: passing. Next due date resets when approved.