Backflow assembly test: 9037 Ridgeview Rd

Approved

Filed Sep 28, 2023 by Drew Kessler, Heritage Backflow Testing. Filed from a phone.

Report

Date of service
Sep 28, 2023
Assembly type
PVB
Serial number
A845150
Size
1
Test gauge serial
G-9478
Gauge calibration date
Jun 24, 2023
Check valve 1
7.8 psid
Check valve 1 closed tight
Yes
Check valve 2
2.4 psid
Result
Pass
I certify this report is true and that I performed or supervised the work
Yes

Automatic checks

  • License on file for Drew Kessler, current on the service date
  • All required fields present
  • Address matches parcel 037-77-01109
  • Readings in range, no flags
  • Result: passing. Next due date resets when approved.

Decision

Approved by M. Reviewer. The property's next due date is set and the owner gets a receipt.