Approved

Filed May 27, 2025 by Parker Vance, Valley Backflow Testing. Filed from a phone.

Report

Date of service
May 27, 2025
Assembly type
PVB
Serial number
W608961
Size
1
Test gauge serial
G-9795
Gauge calibration date
Apr 7, 2025
Check valve 1
0.2 psid
Check valve 1 closed tight
No
Check valve 2
3.8 psid
Result
Fail
I certify this report is true and that I performed or supervised the work
Yes

Automatic checks

  • License on file for Parker Vance, current on the service date
  • All required fields present
  • Address matches parcel 037-90-01003
  • Readings in range, no flags
  • Result: needs follow-up. The property stays on the overdue list until a passing report arrives.

Decision

Approved automatically, because nothing was flagged. The property's next due date is set and the owner gets a receipt.

Property

2472 Fox Run Ct
Owner: Jamie Nguyen
Parcel 037-90-01003