Backflow assembly test: 4607 Spring Branch Ln

Filed Nov 21, 2026 by Casey Fairley, Heritage Backflow Testing. Filed from a phone.

Report

Date of service
Nov 21, 2026
Assembly type
RP
Serial number
K641153
Size
3/4
Test gauge serial
G-8995
Gauge calibration date
Aug 15, 2026
Check valve 1
8.5 psid
Check valve 1 closed tight
Yes
Check valve 2
1.1 psid
Relief valve opened at
4.2 psid
Result
Pass
I certify this report is true and that I performed or supervised the work
Yes

Automatic checks

  • License on file for Casey Fairley, current on the service date
  • All required fields present
  • Address matches parcel 041-89-01143
  • Readings in range, no flags
  • Result: passing. Next due date resets when approved.

Decision

Property

4607 Spring Branch Ln
Owner: Riley Ashby
Parcel 041-89-01143