Backflow assembly test: Crossroads Elementary School

Approved

Filed Jun 14, 2025 by Casey Fairley, Heritage Backflow Testing. Filed from a phone.

Report

Date of service
Jun 14, 2025
Assembly type
DC
Serial number
Z764856
Size
1
Test gauge serial
G-6111
Gauge calibration date
Jan 25, 2025
Check valve 1
8.2 psid
Check valve 1 closed tight
Yes
Check valve 2
1.5 psid
Result
Repaired and passed
Repairs made
Replaced check valve 1 rubber
I certify this report is true and that I performed or supervised the work
Yes

Automatic checks

  • License on file for Casey Fairley, current on the service date
  • All required fields present
  • Address matches parcel 041-45-01053
  • Readings in range, no flags
  • Result: passing. Next due date resets when approved.

Decision

Approved by J. Staff. The property's next due date is set and the owner gets a receipt.