Backflow assembly test: Golden Elementary School
ApprovedFiled Jun 1, 2026 by Casey Fairley, Heritage Backflow Testing. Read in from a paper form and confirmed by staff.
Report
- Date of service
- Jun 1, 2026
- Assembly type
- RP
- Serial number
- A382945
- Size
- 4
- Test gauge serial
- G-4946
- Gauge calibration date
- Oct 20, 2025
- Check valve 1
- 7.8 psid
- Check valve 1 closed tight
- Yes
- Check valve 2
- 1.5 psid
- Relief valve opened at
- 3.2 psid
- Result
- Pass
- I certify this report is true and that I performed or supervised the work
- Yes
Automatic checks
- License on file for Casey Fairley, current on the service date
- All required fields present
- Address matches parcel 041-56-01110
- Readings in range, no flags
- Result: passing. Next due date resets when approved.
Decision
Approved by J. Staff. The property's next due date is set and the owner gets a receipt.