Backflow assembly test: 3054 Orchard Dr

Approved

Filed Dec 13, 2024 by Parker Ashby, Valley Backflow Testing. Filed from a phone.

Report

Date of service
Dec 13, 2024
Assembly type
RP
Serial number
K286939
Size
1
Test gauge serial
G-1626
Gauge calibration date
Oct 31, 2024
Check valve 1
3.3 psid
Check valve 1 closed tight
Yes
Check valve 2
1.5 psid
Relief valve opened at
2.4 psid
Result
Pass
I certify this report is true and that I performed or supervised the work
Yes

Automatic checks

  • License on file for Parker Ashby, current on the service date
  • All required fields present
  • Address matches parcel 041-79-01061
  • Readings in range, no flags
  • Result: passing. Next due date resets when approved.

Decision

Approved by M. Reviewer. The property's next due date is set and the owner gets a receipt.