Backflow assembly test: 5181 Stone Gate Rd
ApprovedFiled Dec 21, 2025 by Parker Harlow, Valley Backflow Testing. Filed from a phone.
Report
- Date of service
- Dec 21, 2025
- Assembly type
- RP
- Serial number
- W317125
- Size
- 3/4
- Test gauge serial
- G-9101
- Gauge calibration date
- Oct 23, 2025
- Check valve 1
- 5.6 psid
- Check valve 1 closed tight
- Yes
- Check valve 2
- 3 psid
- Relief valve opened at
- 4.2 psid
- Result
- Pass
- I certify this report is true and that I performed or supervised the work
- Yes
Automatic checks
- License on file for Parker Harlow, current on the service date
- All required fields present
- Address matches parcel 041-62-01150
- Readings in range, no flags
- Result: passing. Next due date resets when approved.
Decision
Approved automatically, because nothing was flagged. The property's next due date is set and the owner gets a receipt.