Backflow assembly test: 8362 Old Church Ct

Approved

Filed Nov 24, 2025 by Parker Ashby, Valley Backflow Testing. Filed from a phone.

Report

Date of service
Nov 24, 2025
Assembly type
RP
Serial number
K900466
Size
1
Test gauge serial
G-7833
Gauge calibration date
Aug 1, 2024
Check valve 1
0.1 psid
Check valve 1 closed tight
No
Check valve 2
3 psid
Relief valve opened at
3.4 psid
Result
Fail
I certify this report is true and that I performed or supervised the work
Yes

Automatic checks

  • License on file for Parker Ashby, current on the service date
  • All required fields present
  • Address matches parcel 041-90-01332
  • Test gauge calibration is more than a year old.
  • Result: needs follow-up. The property stays on the overdue list until a passing report arrives.

Decision

Approved by M. Reviewer. The property's next due date is set and the owner gets a receipt.

Property

8362 Old Church Ct
Owner: Blake Fairley
Parcel 041-90-01332