Backflow assembly test: 5522 Mill Creek Way

Approved

Filed Oct 10, 2026 by Avery Wexler, Northstar Backflow Testing. Filed from a phone.

Report

Date of service
Oct 10, 2026
Assembly type
RP
Serial number
W291679
Size
1
Test gauge serial
G-1278
Gauge calibration date
Mar 4, 2026
Check valve 1
4.2 psid
Check valve 1 closed tight
Yes
Check valve 2
4 psid
Relief valve opened at
3.2 psid
Result
Pass
I certify this report is true and that I performed or supervised the work
Yes

Automatic checks

  • License on file for Avery Wexler, current on the service date
  • All required fields present
  • Address matches parcel 041-55-01161
  • Readings in range, no flags
  • Result: passing. Next due date resets when approved.

Decision

Approved by J. Staff. The property's next due date is set and the owner gets a receipt.

Property

5522 Mill Creek Way
Owner: Alex Okafor
Parcel 041-55-01161