Backflow assembly test: 891 Pine Knoll Trl
ApprovedFiled Mar 1, 2025 by Casey Fairley, Heritage Backflow Testing. Filed from a phone.
Report
- Date of service
- Mar 1, 2025
- Assembly type
- PVB
- Serial number
- W844435
- Size
- 3/4
- Test gauge serial
- G-6101
- Gauge calibration date
- Oct 20, 2024
- Check valve 1
- 5.6 psid
- Check valve 1 closed tight
- Yes
- Check valve 2
- 2.3 psid
- Result
- Pass
- I certify this report is true and that I performed or supervised the work
- Yes
Automatic checks
- License on file for Casey Fairley, current on the service date
- All required fields present
- Address matches parcel 041-70-01170
- Readings in range, no flags
- Result: passing. Next due date resets when approved.
Decision
Approved by M. Reviewer. The property's next due date is set and the owner gets a receipt.