Backflow assembly test: 7231 Cedar Hollow Trl

Approved

Filed Oct 22, 2026 by Avery Wexler, Northstar Backflow Testing. Filed from a phone.

Report

Date of service
Oct 22, 2026
Assembly type
PVB
Serial number
A600933
Size
3/4
Test gauge serial
G-5887
Gauge calibration date
Jan 1, 2026
Check valve 1
6.7 psid
Check valve 1 closed tight
Yes
Check valve 2
1.2 psid
Result
Repaired and passed
Repairs made
Replaced check valve 1 rubber
I certify this report is true and that I performed or supervised the work
Yes

Automatic checks

  • License on file for Avery Wexler, current on the service date
  • All required fields present
  • Address matches parcel 041-99-01276
  • Readings in range, no flags
  • Result: passing. Next due date resets when approved.

Decision

Approved by M. Reviewer. The property's next due date is set and the owner gets a receipt.

Property

7231 Cedar Hollow Trl
Owner: Reese Okafor
Parcel 041-99-01276