Back to the backflow review queue

Backflow assembly test: 3279 Old Church Dr

Approved

Filed Sep 21, 2023 by Morgan Pruitt, Valley Backflow Testing. Filed from a phone.

Report

Date of service
Sep 21, 2023
Assembly type
RP
Serial number
W129426
Size
1
Test gauge serial
G-7728
Gauge calibration date
Jul 18, 2023
Check valve 1
7.6 psid
Check valve 1 closed tight
Yes
Check valve 2
3.6 psid
Relief valve opened at
2.4 psid
Result
Pass
I certify this report is true and that I performed or supervised the work
Yes

Automatic checks

  • License on file for Morgan Pruitt, current on the service date
  • All required fields present
  • Address matches parcel 041-98-01326
  • Readings in range, no flags
  • Result: passing. Next due date resets when approved.

Decision

Approved automatically, because nothing was flagged. The property's next due date is set and the owner gets a receipt.

Property

3279 Old Church Dr
Owner: Blake Wexler
Parcel 041-98-01326