Back to the backflow review queue

Backflow assembly test: 8677 Old Church Ln

Approved

Filed Feb 16, 2025 by Quinn Nguyen, Northstar Backflow Testing. Read in from a paper form and confirmed by staff.

Report

Date of service
Feb 16, 2025
Assembly type
RP
Serial number
Z932621
Size
3/4
Test gauge serial
G-3231
Gauge calibration date
Jun 26, 2024
Check valve 1
5.5 psid
Check valve 1 closed tight
Yes
Check valve 2
1 psid
Relief valve opened at
4.2 psid
Result
Pass
I certify this report is true and that I performed or supervised the work
Yes

Automatic checks

  • License on file for Quinn Nguyen, current on the service date
  • All required fields present
  • Address matches parcel 041-95-01086
  • Readings in range, no flags
  • Result: passing. Next due date resets when approved.

Decision

Approved by M. Reviewer. The property's next due date is set and the owner gets a receipt.

Property

8677 Old Church Ln
Owner: Drew Harlow
Parcel 041-95-01086