Back to the backflow review queue

Backflow assembly test: 9260 Mill Creek Way

Approved

Filed Dec 28, 2025 by Morgan Pruitt, Valley Backflow Testing. Read in from a paper form and confirmed by staff.

Report

Date of service
Dec 28, 2025
Assembly type
RP
Serial number
A954446
Size
1
Test gauge serial
G-9896
Gauge calibration date
Jun 15, 2025
Check valve 1
4.5 psid
Check valve 1 closed tight
Yes
Check valve 2
1.5 psid
Relief valve opened at
2.8 psid
Result
Pass
I certify this report is true and that I performed or supervised the work
Yes

Automatic checks

  • License on file for Morgan Pruitt, current on the service date
  • All required fields present
  • Address matches parcel 041-39-01187
  • Readings in range, no flags
  • Result: passing. Next due date resets when approved.

Decision

Approved by J. Staff. The property's next due date is set and the owner gets a receipt.

Property

9260 Mill Creek Way
Owner: Blake Benton
Parcel 041-39-01187