Back to the backflow review queue

Backflow assembly test: 5275 Mill Creek Way

Approved

Filed Mar 30, 2026 by Morgan Pruitt, Valley Backflow Testing. Filed from a phone.

Report

Date of service
Mar 30, 2026
Assembly type
RP
Serial number
Z315888
Size
1
Test gauge serial
G-8445
Gauge calibration date
Oct 23, 2025
Check valve 1
6.1 psid
Check valve 1 closed tight
Yes
Check valve 2
1.7 psid
Relief valve opened at
2.9 psid
Result
Pass
I certify this report is true and that I performed or supervised the work
Yes

Automatic checks

  • License on file for Morgan Pruitt, current on the service date
  • All required fields present
  • Address matches parcel 041-12-01049
  • Readings in range, no flags
  • Result: passing. Next due date resets when approved.

Decision

Approved by J. Staff. The property's next due date is set and the owner gets a receipt.

Property

5275 Mill Creek Way
Owner: Cameron Danner
Parcel 041-12-01049