Back to the backflow review queue
Backflow assembly test: 9667 Cedar Hollow Ln
ApprovedFiled Dec 19, 2023 by Morgan Pruitt, Valley Backflow Testing. Filed from a phone.
Report
- Date of service
- Dec 19, 2023
- Assembly type
- RP
- Serial number
- W100853
- Size
- 3/4
- Test gauge serial
- G-8801
- Gauge calibration date
- Sep 5, 2022
- Check valve 1
- 0.2 psid
- Check valve 1 closed tight
- No
- Check valve 2
- 2.6 psid
- Relief valve opened at
- 3.5 psid
- Result
- Fail
- I certify this report is true and that I performed or supervised the work
- Yes
Automatic checks
- License on file for Morgan Pruitt, current on the service date
- All required fields present
- Address matches parcel 041-35-01258
- Test gauge calibration is more than a year old.
- Result: needs follow-up. The property stays on the overdue list until a passing report arrives.
Decision
Approved by M. Reviewer. The property's next due date is set and the owner gets a receipt.
Property
9667 Cedar Hollow Ln
Owner: Quinn Wexler
Parcel 041-35-01258