Backflow assembly test: 4195 Hickory Dr

Approved

Filed Mar 30, 2024 by Parker Harlow, Valley Backflow Testing. Filed from a phone.

Report

Date of service
Mar 30, 2024
Assembly type
RP
Serial number
Z901731
Size
3/4
Test gauge serial
G-8631
Gauge calibration date
Jan 12, 2024
Check valve 1
5.4 psid
Check valve 1 closed tight
Yes
Check valve 2
2 psid
Relief valve opened at
3 psid
Result
Pass
I certify this report is true and that I performed or supervised the work
Yes

Automatic checks

  • License on file for Parker Harlow, current on the service date
  • All required fields present
  • Address matches parcel 041-31-01042
  • Readings in range, no flags
  • Result: passing. Next due date resets when approved.

Decision

Approved by M. Reviewer. The property's next due date is set and the owner gets a receipt.

Property

4195 Hickory Dr
Owner: Riley Fairley
Parcel 041-31-01042