Backflow assembly test: 4195 Hickory Dr
ApprovedFiled Apr 30, 2026 by Quinn Nguyen, Northstar Backflow Testing. Filed from a phone.
Report
- Date of service
- Apr 30, 2026
- Assembly type
- RP
- Serial number
- Z901731
- Size
- 3/4
- Test gauge serial
- G-2938
- Gauge calibration date
- Dec 10, 2025
- Check valve 1
- 7.4 psid
- Check valve 1 closed tight
- Yes
- Check valve 2
- 1.3 psid
- Relief valve opened at
- 4.2 psid
- Result
- Pass
- I certify this report is true and that I performed or supervised the work
- Yes
Automatic checks
- License on file for Quinn Nguyen, current on the service date
- All required fields present
- Address matches parcel 041-31-01042
- Readings in range, no flags
- Result: passing. Next due date resets when approved.