Back to the backflow review queue

Backflow assembly test: 758 Ridgeview Way

Approved

Filed Dec 31, 2025 by Parker Harlow, Valley Backflow Testing. Filed from a phone.

Report

Date of service
Dec 31, 2025
Assembly type
RP
Serial number
B454024
Size
3/4
Test gauge serial
G-7249
Gauge calibration date
Mar 9, 2025
Check valve 1
3.9 psid
Check valve 1 closed tight
Yes
Check valve 2
2 psid
Relief valve opened at
2.5 psid
Result
Pass
I certify this report is true and that I performed or supervised the work
Yes

Automatic checks

  • License on file for Parker Harlow, current on the service date
  • All required fields present
  • Address matches parcel 041-77-01335
  • Readings in range, no flags
  • Result: passing. Next due date resets when approved.

Decision

Approved automatically, because nothing was flagged. The property's next due date is set and the owner gets a receipt.

Property

758 Ridgeview Way
Owner: Taylor Okafor
Parcel 041-77-01335