Back to the backflow review queue
Backflow assembly test: 3016 Hickory Trl
ApprovedFiled Jun 23, 2024 by Avery Ramirez, Heritage Backflow Testing. Filed from a phone.
Report
- Date of service
- Jun 23, 2024
- Assembly type
- DC
- Serial number
- K597627
- Size
- 1
- Test gauge serial
- G-1022
- Gauge calibration date
- Feb 14, 2024
- Check valve 1
- 3.1 psid
- Check valve 1 closed tight
- Yes
- Check valve 2
- 1.2 psid
- Result
- Pass
- I certify this report is true and that I performed or supervised the work
- Yes
Automatic checks
- License on file for Avery Ramirez, current on the service date
- All required fields present
- Address matches parcel 051-15-01209
- Readings in range, no flags
- Result: passing. Next due date resets when approved.
Decision
Approved by J. Staff. The property's next due date is set and the owner gets a receipt.
Property
3016 Hickory Trl
Owner: Jamie Harlow
Parcel 051-15-01209